The paper illustrates the status quo of a research project for the development of a control system enabling CHP units for a demand-oriented electricity production by an intelligent management of the heat storage tank. Thereby the focus of the project is twofold. One is the compensation of the fluctuating power production by the renewable energies solar and wind. Secondly, a reduction of the load on the power grid is intended by a better match of local electricity demand and production. In detail, the general control strategy is outlined, the method utilized for forecasting heat and electricity demand is illustrated as well as a correlation method for the temperature distribution in the heat storage tank based on a Sigmoid function is proposed. Moreover, the simulation model for verification and optimization of the control system and the two field test sites for implementing and testing the system are introduced.
Nowadays CHP units are discussed for the production of electricity on demand rather than for generation of heat providing electricity as a by-product. By this means, CHP units are capable of satisfying a higher share of the electricity demand on-site and in this new role, CHP units are able to reduce the load on the power grid and to compensate for high fluctuations of solar and wind power.
Evidently, a novel control strategy for CHP units is required in order to shift the operation oriented at the heat demand to an operation led by the electricity demand. Nevertheless, the heat generated by the CHP unit needs to be utilized completely in any case, for maintaining energy as well as economic efficiency. Such a strategy has been developed at Reutlingen University, and it will be presented in the paper. Part of the strategy is an intelligent management for the thermal energy storage (TES) ensuring that the storage is at low level in terms of its heat content just before an electricity demand is calling the CHP unit into operation. Moreover, a proper forecast of both, heat and electricity demand, is incorporated and the requirements of the CHP unit in terms of maintenance and lifetime are considered by limiting the number of starts and stops per unit time and by maintaining a certain minimum length of the operation intervals.
All aspects of this novel control strategy are revealed in the paper, which has been implemented on a controller for further testing at two sites in the field. Results from these tests are given as well as results from a simulation model, which is able to evaluate the performance of the control strategy for an entire year.